FLOWMETER SELECTION GUIDE

 

Clean Liquid

Dirty Liquid

Slurry

Viscous Liquid

Corrosive/
Erosive
Liquid

Clean Gas

Dirty Gas

Steam

Full
Bore Size Availability

Type Of Measurement

Accuracy

Typical Rangeability

Reynolds No. or Other limitations

Sensitivity To Installation Effects

Straight Piping Requirements

Typical Ancillary Equipment

Other Considerations

Preferred Meter Orientation

Initial Cost

Installation Cost

Maintenance Cost

Operating Cost

Performance Stability

Standards Or Recommended Practice

Concentric OP (Square Edged)

G

L

X

X

L

G

L

G

> 1 in.  > 25mm

Square Root Volumetric

0.5%     to     3%

3:1     to    5:1

>10,000

High

10D to 40D-UP 2D to 6D Down

Drain, Vent Blow-off-and  S/D valves

Pressure and/or Temp. Compensation May be Required

Pressure Tap Orientation Depends on Pipe Orientation & Fluid Being Metered

L TO H

M TO H

M TO H

M TO H

Performance Affected by Edge and Tap Wear

AGA3, ANSI/API 2530 ANSI/ASME MFC 3M. ISO 5167 AESME Fluid Meters

Segmental Wedge

G

G

G

G

G

G

G

G

> 1/2 in. > 15mm

Square Root Volumetric

0.5%     to     5%

3:1     to    5:1

>500

Low

5D to 10D-UP 2D to 5D Down

None with Remote Seal Version

Same as Orifice Plate

No Limitations on Remote Seal Elements

H

L

L

L TO M

GOOD

-----------------------------

Venturi Tube

G

G

L

X

L

G

G

G

> 2 in.  > 50mm

Square Root Volumetric

0.5%     to     1.5%

3:1     to    5:1

>100,000

Low

Upstream Runs Shorter Than OP by Factor 2-9Times

Same as OP, Air Purge & Vent Cleaners on Dirty Liquids

Same as Orifice Plate

Same as Orifice Plate

M TO H

M

L

L

GOOD

AGA3, ANSI/API 2530 ANSI/ASME MFC 3M. ISO 5167 AESME Fluid Meters

Flow Nozzle

G

L

X

X

L

G

L

G

> 2 in.  > 50mm

Square Root Volumetric

1%     to     2%

3:1     to    5:1

>75,000

Mod

Same as for Orifice Plate

Same as Orifice Plate

Same as Orifice Plate

Same as Orifice Plate

M TO H

M

L

M

GOOD

Same as Venturi Tube

V-Cone

G

L

L

L

L

G

L

G

1 to 16 in. 25 to 400mm

Square Root Volumetric

0.5%     to     2%

3:1     to    5:1

>4,000

Low

5 to 10D-up

Same as Orifice Plate

Same as Orifice Plate

-----------------------------

 M   

M TO H

M

M

GOOD

-----------------------------

Oscillating Vane

G

L

X

L

G

X

X

X

1,2,3 in. 25,50,75  mm

Linear Volumetric

0.5%

10:1

Flow Range fixed for a given size

Mod To High

10 to 30D-UP 5D-Down

-------------

-------------------------

Flow Should be Upward in Vertical Installations

L

L

L TO M

M

Sensor Assembly Requires Periodic Replacement

-----------------------------

Target

G

G

G

G

L

G

G

L

> 1/2 in.  >15mm

Square Root Volumetric

0.5%     to     5%

3:1     to   20:1

>1,000

High

Same as for Orifice Plate

-------------

Viscosity Affects Performance Below Critical Rd.

Zero May Need Adjustment in Vertical Installations

L TO M

L

M TO H

M

Performance Affected by Wear of Target

-----------------------------

Varaible Area

G

L

X

L

L

G

L

L

< 3 in.   < 75mm

Linear Volumetric

0.5%     to     5%

10:1

Fluids      Under          3 Cp

None

None

-------------

-------------------------

Can Only Be Installed             In Vertical Pipe with Flow Up

L TO M

L

L

M

GOOD

-----------------------------

Magnetic

G

G

G

G

G

X

X

X

>1/16 in.  > 1mm

Linear Volumetric

0.2%     to     2%

30:1 to   100:1

None

Low

5 to 10D-UP   3D-Down

Block Valves May be Required to isolate Meter For Servicing

AC Designs May Give Better Performance On Some Slurries

Electrodes Musty Be In Horizontal Plane. Flow should be Upwards in Vertical Installation

M TO H

L TO M

L TO M

L

GOOD

ISO 6817

Vortex

G

L

X

X

L

G

L

G

1/2 to 12in. 15 to300mm

Linear Volumetric

0.5%     to   1.5%

10:1     to   20:1

>20,000

High

Same as for Orifice Plate With 0.70 Beta

Block Valves May be Required to isolate Meter For Servicing

Indicates Zero Flow Below Cut-off

-----------------------------

M

L TO M

L TO M

M

GOOD

ANSI/ASME MFC 6M

Turbine

G

L

X

L

L

G

L

G

> 1/4 in.   > 6mm

Linear Volumetric

0.1%     to   1%

10:1     to   50:1

Fluids      Under          10 CST

High

Similar To Orifice Plate

Strainers, Filters, Air Eliminators, Steam Taps May be Required

Viscosity Can Affect Performance

Some Designs Must Be Oriented as Calibrated

L TO H

M TO H

M TO H

M

Performance Affected by Wear of Bearings & other Parameters

AGA7, API 2534 ISO 2715 ASME Fluid Meters, API Manual for Petroleum Measurement Standards

Doppler

X

G

G

L

G

X

X

X

> 1/2 in.  >15mm

Linear Mass Volumetric

1%     to   5%

 > 10:1  

Fluids          Must Have   Suspensoids

High

Similar To Orifice Plate

-------------

May Have Problems on Concentrated Slurries

Transducers Must Be In Horizontal Plane

L TO H

L TO H

L

L

GOOD

-----------------------------

Transit Time

G

X

X

L

G

G

X

L

> 1/2 in.  >15mm

Linear Mass Volumetric

1%     to   5%

 > 10:1  

Fluids      Must Be     Clean

High

Similar To Orifice Plate

-------------

May Have Problems on Dirty Fluids

Transducers Must Be In Horizontal Plane

L TO H

L TO H

L

L

GOOD

ANSI/ASME MFC-YY

Coriolis Type

G

G

G

G

L

L

L

X

< 6 in.    <150mm

Linear Mass Volumetric

0.15% to     2%

40:1 to  100:1

None

None

None

Special Supports May be Required For Meters

Entrained Air May Cause Problems

Specific Orientations Vary With Meter Designs

H

L TO M

L

L TO H

GOOD

ANSI/ASME MFC-11M,   California Weights & Standards Bureau

Thermal Dispersion

X

X

X

X

X

G

L

G

< 3 in.   < 75mm

Logrithmic Mass

1%     to   5%

upto100:1

None

Mod To High

10 to 20D-UP  

-------------

May Need To Provide Compensation for Wide TEMP. Ranges

Some Types Require Same Orientation as in Calibration 

L TO M

L TO M

L

L TO M

Performance Affected by severe Build-up on Sensor for Immersion Types

-----------------------------

G = GOOD
L = LIMITED APPLICATION
X = NOT RECOMMENDED
L  = LOW
M = MODERATE
H = HIGH